9 appendix – OSRAM QUICKTRONIC INTELLIGENT DIM CFL User Manual

Page 81

background image

80

9.1

Starting currents and max. number of ECGs in automatic cutouts

Figure 51: Starting currents and max. number of ECGs in automatic
cutouts (B characteristic), measurement at U

N

= 230 V

AC

9.1.1 Minimum B/C characteristic triggering levels

The minimum triggering levels increase from B to C characteristic by
the factor = 1.67, i.e. not quite a factor of 2. At the same time, how-
ever, the total current must not exceed the value of the automatic
cutouts.

9 Appendix