OSRAM QUICKTRONIC INTELLIGENT DIM CFL User Manual
Page 13

12
Note (acc. to DIN VDE 0100/11.85, T 520, Sect. 528.11):
•
•
Cables or lines that are insulated for the maximum operating
voltage must be used, or each conductor of a multi-wire cable/
line must be insulated for the next voltage appearing in the
cable/line.
•
•
When laying conductor lines in electrical installation pipes or
ducts only the conductors of a main power circuit including the
associated auxiliary power circuit may be laid together
•
•
Several main power circuits including the associated auxiliary
power circuits can also be combined in a single cable or line
•
Cables and terminals approved for use the mains voltage (230 V)
must be used for the installation
•
The installation must be carried out in such a way that when the
supply voltage is switched off, all signal and control cables are also
switched off at the same time
•
All components of the main power and control power circuits must
be designed for 250 V working voltage to ground
•
All the luminaires must be wired with H05 cables provided U
OUT
does not exceed 430 V
eff,
and also be subjected to an insulation
test (in accordance with VDE) in conjunction with OSRAM DALI/
DIM ECGs. OSRAM QUICKTRONIC DALI/DIM ECGs do not ex-
ceed 430 V
eff
even for T5-Ø 16 mm HE and HO florescent lamps.