Note (acc. to DIN VDE 0100/11.85, T 520, Sect. 528.11):

Cables or lines that are insulated for the maximum operating

voltage must be used, or each conductor of a multi-wire cable/
line must be insulated for the next voltage appearing in the
cable/line.

When laying conductor lines in electrical installation pipes or

ducts only the conductors of a main power circuit including the
associated auxiliary power circuit may be laid together

Several main power circuits including the associated auxiliary

power circuits can also be combined in a single cable or line

Cables and terminals approved for use the mains voltage (230 V)
must be used for the installation

The installation must be carried out in such a way that when the
supply voltage is switched off, all signal and control cables are also
switched off at the same time

All components of the main power and control power circuits must
be designed for 250 V working voltage to ground

All the luminaires must be wired with H05 cables provided U

OUT

does not exceed 430 V

eff,

and also be subjected to an insulation

test (in accordance with VDE) in conjunction with OSRAM DALI/
DIM ECGs. OSRAM QUICKTRONIC DALI/DIM ECGs do not ex-
ceed 430 V

eff

even for T5-Ø 16 mm HE and HO florescent lamps.