OSRAM EASY PB Coupler User Manual
Easy pb coupler, Pushbutton coupler operating instructions, Description
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40083219155974
4008321915597
Page 1 of 2
Pushbutton coupler
Operating instructions
IV 2009
EASY_PB_Coupler_ba0904en_we1.01.indd
EASY PB Coupler
1
2
3
4
S1
S2
S3
S4
T1
GND
T2 T3 T4
GND
T5
T8 T7 T6
C
A
A
B
D
Description
Function and application
The EASY PB Coupler is connected to an EASY control unit
via the supplied Y-connector and thus enables the connection
of standard pushbuttons, switches, motion detectors or timer
switches with a potential-free closer contact to an EASY light
control system.
The EASY PB coupler is installed in a flush device box behind
the respective switch insert, pushbutton insert or distributor box.
Function
The EASY PB Coupler converts the button or switch opera-
tions to corresponding digital telegrams and transmits them
to the control units of type DALI EASY II or OT EASY 60. The
functions of the connected pushbuttons or switch contacts are
assigned by means of the DIP switch setting.
The EASY PB Coupler is operated with safety extra low voltage
and is directly supplied over the EASY signal line. An additional
supply is not necessary.
Design
The pushbutton coupler is made up of the following compo-
nents:
• Connection terminals T1 to T8 for up to eight pushbuttons,
switches or potential-free contacts (A)
• DIP switches (B)
• Connection terminals for signal lines (C)
• Housing (D)
Operation
Function of the DIP switches
The functions of the connected pushbuttons or switch contacts
are assigned by the positions of the DIP switches.
Operation via pushbuttons
Note: Operation via pushbuttons is analogous to operation via a
remote control. See the separate instructions of the DALI EASY
II and OT EASY 60 control units.
Disabling of lighting scene storage
Storing of scenes can be disabled by means of DIP switch 1.
On
On
Scene storage is disabled
Scene storage is enabled
Pure lighting scene operation
Short press:
The corresponding scene is called up.
Long press:
The current lighting situation is stored.
Continuous press:
As long as the pushbutton is pressed, consecutive scenes are
called up at intervals of 2 s.
On
On
T 1...8
Store and call up
lighting scenes 1...8
Store and call up lighting
scenes 9...16
Lighting scene, channel and central unit operation
Short press:
The selected channel or the entire lighting is switched on or off.
Long press:
Brightness is changed manually. The dimming direction
changes with every long press.
On
On
T 1...4
Luminaire groups (channels) 1...4:change bright-
ness manually/switch on and off
T 5
All luminaires: change brightness manually/switch
on and off
T 6…8
Store and call up
lighting scenes 1...3
Store and call up lighting
scenes 4...6