OSRAM QUICKTRONIC INTELLIGENT DIM CFL User Manual
Page 39
38
For emergency lighting/voltage loss
13
in the DALI controllers two val-
ues can be configured/programmed separately for each unit (e.g. us-
ing the OSRAM DALI Luminaire Tool DLT).
•
System failure level: Emergency operation (1…100 % light), de-
tected by switching off the control line
•
Power on level: Light value after the mains voltage is restored
(1…100 % light)
The system failure level always has priority over the power on level,
especially when switching over (in the event of a brief power out-
age, emergency operation is therefore ensured). The factory setting
for both values is 100 % light.
Typical data for the QUICKTRONIC INTELLIGENT DALI family impor-
tant for emergency lighting systems are*:
Starting time of the lamp (max.)
0.6 s
Permissible voltage range (DC)
154…276 V
Min. voltage for lamp start (DC)
198 V
Permissible voltage range (AC)
198…264 V
Mains frequency
0, 50…60 Hz
Table
5: OSRAM ECG data for emergency operation of the lighting
system
*Further technical data of the respective ECG type can be found in the
corresponding datasheet or on our homepage at www.osram.com/qti.
The DALI or dimming function of the QTi DALI … DIM is identical in AC
and DC operation.
13
•
During power outages < 200 ms, the light stays on (no light failure) because
the ECGs are not preheated again.
•
During power outages > 200 ms, the ECGs go through the entire preheat-
ing cycle. The following applies to the QTi DALI/DIM and HF DIM family: The
starting time in HO lamps is 0.5 s and in HE lamps it is 0.7 s. DALI ECGs
require an additional 0.5 s for initialization