What insulation is required for the DALI control line?

The DALI control line must be approved for mains voltage (as in the

case of the 1…10 V interface).

Can existing 1…10 V control lines be used?

Yes, provided they are rated for mains voltage.

How long can a control line be?

A maximum of 300 m between the controller and the furthest con-

nected DALI unit.

Can control and power cables be laid together?

Yes, a 5 x 1.5 mm

2

NYM cable can be used, for example.

What line cross section must the control line have?

Up to 100 m: min. 0.5 mm

2

/from 100 m to 150 m: 1.0 mm

2

/from

150 m: 1.5 mm

2

.

Can any company develop a DALI controller or DALI ECG?

Yes, there are no restrictions except that the DALI logo

may only be used by members of the DALI Activity Group.
See also http://www.dali-ag.org/.

What happens if I use DALI ECGs from different manufactur-
ers in the same system?

The controllers are DALI-compatible if they carry the DALI logo. It is

important to note, however, as in 1…10 V technology, ECGs from
different manufacturers can result in different filament preheating
times and different lamp starting times.

Can controllers from different manufacturers be combined?

No, DALI ECGs are interchangeable, but the control components

cannot normally be combined.

Is it possible to limit the maximum and minimum luminous
flux?

Yes, these values can be changed/limited with the appropriate

controller in the ECG.