beautypg.com

OSRAM QUICKTRONIC INTELLIGENT DIM CFL User Manual

Page 29

background image

28

2.9.1 The 1…10 V dimming curve

The 1…10 V interface is defined in IEC 60929. In the control voltage
range of 3 V

to 10 V there is a largely linear relationship to the rela-

tive luminous flux. In the 1…10 V interface, a logarithmic response
(like the DALI units) is adjusted by a logarithmic potentiometer.

luminous flux

in %

Control voltage in V

Figure 14: The 1…10 V characteristic: Luminous flux against control
voltage

The control current in the 1…10 V interface drops with increasing
control voltage. Unlike the DALI interface, this does not therefore re-
main constant.

Control current

Control voltage [V]

Figure

15: Decreasing control current with increasing control voltage