OSRAM QUICKTRONIC INTELLIGENT DIM CFL User Manual
Page 78

77
2.
The available daylight is sufficiently bright. Cover the sensor and
observe the response of the luminaire.
3.
The motion detection is deactivated for 30 s after the lighting
system has been switched off manually. This time will only expire
if there are no more people in the detection zone.
•
The luminaire is not regulating its the brightness to the set-
point value
1. After setting the brightness, you must press the button twice
inside 30 s (to store the setpoint value). If you press the button
later than that, the holiday mode will be activated.
2.
The dimming was carried out manually – this deactivates the
brightness control. Switch the luminaire off and on again.
3. No setpoint value has been stored.
Set the required light value and double-click to store it.
•
Holiday mode cannot be activated.
The brightness level has been changed within the past 30 seconds
– holiday mode can only be activated after this time.
8.1.5 Troubleshooting DALI controllers
•
The ECGs are not reacting to commands from the controller?
Please check the wiring where approx. 16 V
DC
should be applied to
the DALI terminals of the ECG.
8.1.6 DALI to 1…10 V converter
•
Not all lighting strips can be switched off.
Please check that the power supply of the relevant lighting group
has been routed via the load contact of the respective converter.
8.2
1…10 V DIM ECG part
•
How long can the 1…10 V control line be?
The maximum permissible length of the control line is 100 m (also
applies to the DALI control line). (Note: Due to the low control cur-
rent, a drop in voltage is only noticeable on the control line after
approx. 300-400 m)
•
What line cross section should the 1…10 V control line
have?
1.5 mm² is recommended as the cross section. The insulation of
the line used must be designed for mains voltage.