Light and motion sensor
Fitting instructions
VI 2011
LSPD_MULTI3-A_A-w_ma1106_en_we1.01.indd
LS/PD MULTI 3 A
LS/PD MULTI 3 A-w
Description
Purpose and application
The LS/PD MULTI 3 A sensor detects the presence of persons
and measures the intensity of ambient light.
The sensor is available in two colours:
• LS/PD MULTI 3 A (anthracite)
• LS/PD MULTI 3 A-w (white)
The sensor is installed in luminaires or can be attached to
luminaires later using a clip (ideal for
T5/T8 louver luminaires).
Installation
Safety instructions
The sensor must only be installed and put into operation by
a qualified electrician. The applicable safety regulations and
accident prevention regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
• Only work on the sensor when it is de-energised.
CAUTION!
Destruction of the sensor and other devices through
incorrect mounting!
• Only use OSRAM control units of the following
types: DALI MULTI 3/DIM MULTI 3, DALI
MULTIeco/MULTIeco, DALI PROFESSIONAL
Sensor Coupler.
• Do not connect control line with external voltage.
• Do not exceed the maximum total line length.
• Do not route the sensor line together with the
power or lamp line.
Design
The sensor is made up of the following components:
• Light sensor (A)
• Motion sensor (B)
• LED (C)
• Connection cable (D)
• Housing (E)
A B C
E
D
Connecting the sensor
Connect the sensor using the supplied cable or a commercially
available 4-pin cable. If the cable is shortened or lengthened,
ensure that the wiring is correct.
Sensors can be connected in parallel via a Y-branch. For the
maximum number of sensors: see the separate control unit
manual.
F Y-branch
G Sensor
DALI MULTI 3
Sensor
F
G