beautypg.com

VEGA VEGACOM 557 Profibus DP User Manual

Page 48

background image

48

VEGACOM 557 Profibus DP

Providing of input and output addresses for VEGACOM 557

Setup

Length

Operating mode

input section (Byte)

Output section (Byte)

50 Byte IN, 2 Byte OUT

50

2

(50E2A)

6 Byte IN, 6 Byte OUT

6

6

(6E6A)

The planned output and input addresses are
important when using the example project on

the utility diskette. In the example project

(enquiry of FB 220) the two addresses must

be transferred as enquiry parameters (see

also „s7_doku.pdf“ on the utility diskette).

After the Profibus-Slave VEGACOM 557 has

been planned and the PLC loaded, the bus

error LED on the Profibus-Master must extin-

guish and the green „BA“-LED on VEGACOM
557 must light per manently. If this occurs, the

Profibus communication between PLC and

VEGACOM 557 is functioning.

Example projects on the utility diskette

An example program for the operating mode
50E2A and an example pr ogram for the oper -

ating mode 6E6A is available on the utility

diskette for reading measured values out of

VEGACOM 557. Further information on con-

figuration and function are included in the
PDF file „s7-doku.pdf“. To view the file, the

„Akrobat Reader “ is required. Please contact

VEGA Grieshaber KG if you need further

example programs or assistance.