VEGACOM 557 Profibus DP

Measured value image LOGBUS in mode 6E6A

In this operating mode, the PC/DCS values can be read out individually in VEGACOM 557, i.e.

the Profibus-Master enquires a measured value and the VEGACOM 557 delivers this meas-

ured value.

Control command 0xCD (LOGBUS)

When enquiring with this control command, VEGACOM 557 answers with an individual PC/

DCS value. The enquiry telegram, written by the Profibus-Master into the 6 Byte outputs is
structured as follows:

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

control

command

reserved

PC/DCS

number

reserved

reserved

reserved

0xCD

1...255

0xFF

0xFF

0xFF

0xFF

6 Byte

Format of the enquiry acc. to individual PC/DCS values

VEGACOM 557 writes the following answering telegram into the 6 Byte input of the Profibus-

Master:

6 Byte

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Status

Highword

Lowword

Add. info

0xYY

1...255

0x00

0x00

0xHH

0xLL

PC/DCS

number

PC/DCS measured value

Format of the VEGACOM 557 answer

Status:

0x00 = valid measured value
0x01 = simulated m easured v alue ( only o n

VEGAMET 509 and 512)

0x80 = old measured value (probably con-

nection separated)

0xFE = no PC/DCS value available (not

configured)

0xFF = general error

Data image in VEGACOM 557

PC/DCS measured value

0xHH = High-Byte of the measured value
0xLL = Low-Byte of the measured value

Value section comprises max. +32.768 to

-32.767.