VEGA KLD2-PL-Ex1.PA Power-Link for PROFIBUS DP-PA segment coupler SK2 User Manual
Kld2-pl-ex1.pa power-link, Composition
1
096
79
0_
EN
G.xm
l
2
003
-02-
2
7
Subject to reasonable modifications due to technical advances.
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
KLD2-PL-Ex1.PA
Power-Link
Power rail
Power
Saf
e area
Hazar
dous area
Connection to gateway
CH 1 ... 4
PROFIBUS-PA segment
[EEx ia] IIC
+
FE
-
S
+
-
+
-
16
1
17
2
41
CH
40
42S
59
60
58
18
3
Z
Composition
Power-Link for an intrinsically safe
PROFIBUS PA segment
• PROFIBUS PA according to
EN 50170/2 and IEC 61158-2;
31,25 kbit/s
• Up to 10 Ex devices can be
connected to the PA segment
• Supply via Power Rail
• 24 V DC rated operational voltage
• Removable terminals and Power
Rail
• EMC acc. to NAMUR NE 21
• Field circuit in the hazardous area
EEx ia IIC and Class I, Division 1,
Groups A, B, C and D
Together with the KLD2-GT-DP(R).xPA
Gateway, the Power-Link forms an SK2
Segment Coupler and can only be operat-
ed in association with it. The KLD2-PL-
Ex1.PA can be installed in Zone 2. The
Power-Link thus provides the intrinsically
safe interface. The PROFIBUS PA sta-
tions are supplied from the Power-Link via
the bus.
Data exchange between the Power-Link
and channel 1 of the KLD2-GT-
DP(R).xPA gateway takes place via the
power rail. If the Power-Link is operated
with channel 2, 3 or 4 of the gateway, a
wire connection for the data exchange
must be provided between the Power-Link
and the gateway, via the removable termi-
nals.
The communication of the SK2 segment
coupler behaves transparently. The Pow-
er-Link does not have to be configured.
The baud rate of the intrinsically safe
PROFIBUS PA segment is 31.25 kbit/s,
in accordance with IEC61158-2.
Please note!
Information on the commissioning of the
Profibus PA can be obtained from the
guidance documentation of the PROFI-
BUS User Organisation.
•
Function
Power-Link for PROFIBUS DP/PA segment coupler SK2