VEGA VEGACOM 557 Profibus DP User Manual

Page 35

background image

VEGACOM 557 Profibus DP

35

Data image in VEGACOM 557

Measured value image DISBUS in mode 6E6A

In this operating mode, it is possible to read out the PC/DCS values individually in VEGACOM

557, i.e. the Profibus-Master enquires a measured value and this measured value is provided

by the VEGACOM 557.

Control command 0xCD (DISBUS)

When enquiring with this control command, VEGACOM 557 answers with individual PC/DCS

value. The enquiry telegram written by the Profibus-Master into the 6 Byte outputs is struc-
tured as follows.

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

control

command

VEGA-

MET

address

reserved

PC/DCS

number

reserved

reserved

reserved

0xCD

1...15

1...7

0xFF

0xFF

0xFF

0xFF

6 Byte

Format of the enquiry acc. to individual PC/DCS values

VEGACOM 557 writes the following answering telegram into the 6 Byte inputs of the Profibus-

Master:

6 Byte

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Status

Highword

Lowword

Add. info

0xYY

1...15

1...7

0x00

0x00

0xHH

0xLL

VEGA-

MET

address

PC/DCS

number

PC/DCS measured value

Format of the VEGACOM 557 answer

Status:

0x00 = valid measured value

0x01 = simulated m easured v alue ( only o n

VEGAMET 509 and 512)

0x80 = old measured value (probably con-

nection separated)

0xFE = no PC/DCS value available (not

configurated)

0xFF = general error

PC/DCS measured values

0xHH = High-Byte of the measured value

0xLL = Low-Byte of the measured value

Value range comprises max. +32.768 to

-32.767.