8 Setup

8.1 Setup check list

For the setup of VEGACOM 557 on PROFI-

BUS DP proceed as follows:

I. Check hardware requirements

• PROFIBUS DP compatible master compo

nent

• VEGACOM 557 version „Profibus DP “

II. Check software requirements

• VEGA Utility diskette from version 3.00 with

GSD file and programming examples for
Siemens S5, S7

II. Carry out adjustments on VEGACOM
557 (DIL switch on additional board)

• Set Profibus-Slave address

• Activate/deactivate bus terminator

III. Configurate Profibus DP-Master and

check communication

• The green LED named “BA” lights on

VEGACOM 557 with correct communica-

tion.

8.2 Setup SIEMENS S7 automation

system

For connection of decentralised peripherals

to automation instruments of S7 series,
SIEMENS uses Pr ofibus DP. Many of the S7

CPUs offer already a Profibus DP interface.

For connection of VEGACOM 557 to a S7

automation system, a Profibus DP interface

must be available and the automation system
must work as Pr ofibus-Master. In this section,

all measures that must be taken for the setup

of your VEGACOM 557 on a S7 automation

system are described in detail.

Note:

If your Profibus-Master is manufactured by

another company, please check the manu-

facturer documentation for the r equired infor-
mation.

Configuration SIEMENS S7 automation
system

The configuration and parameter setting of

the Profibus is done with the software

SIMATIC-Manager fr om SIEMENS. All con-

figurations for the connected Profibus net-

work are made via the window HW-Config.