VEGACOM 557 Profibus DP

6 Operating mode VEGACOM 557

Operating mode VEGACOM 557

Two different operating modes ar e available

for VEGACOM 557.

Depending on the operating mode, VEGA-

COM 557 reserves a different number of
input and output bytes in the Profibus-Mas-

ter.

6.1 Mode 50E2A

In this mode, VEGACOM 557 reserves 50
input bytes and 2 output bytes.

The Profibus-Master has to process 50 Bytes

of data consistently .

How it works

A control command and a block number (1

byte each) are written into the 2 Byte output
data. After VEGACOM 557 has received

these two Bytes via Pr ofibus DP, it answers

by sending the data of the required block -

these 50 Byte are then available to the Profi-

bus-Master as input bytes.
Since a maximum of 255 PC/DCS values and

up to 32 relay status are available in VEGA-

COM, but only 50 bytes at a time can be

transferred on the Profibus, the data are
multiplexed on the bus.

To facilitate this, the data ar e divided in

VEGACOM 557 into blocks. The requested

block can be enquired by the Profibus-Mas-
ter with the control command and the block

number.

8 PC/DCS values (6 Byte each), the control

command (1 Byte) and the block number (1

Byte) decremented by the value 1 are re-
turned in a block.

6.2 Mode 6E6A

In this mode, VEGACOM 557 reserves 6
input byte and 6 output byte.

The Profibus-Master must process 6 Byte

data consistently.

How it works

A control command and a PC/DCS value

number (1 Byte each) is written by the Profi-
bus-Master into the 6 Byte output data, the

remaining 4 Byte must be filled with the value

0xFF.

After VEGACOM 557 has received these 6
Byte via the Pr ofibus DP, it answers by send-

ing the data of the enquired PC/DCS value.

These 6 Byte are then available as input

bytes to the Pr ofibus-Master.

Since a maximum of 255 PC/DCS values and

up to 32 relay status are available in VEGA-

COM, but only 6 bytes at a time can be

transferred on the Profibus, the data on the

bus are multiplexed.

To facilitate this, the data in VEGACOM 557

are divided into single PC/DCS values. With

the control command and the PC/DCS value

number, the Pr ofibus-Master can enquir e t he
respective PC/DCS value.

6.3 Selection of the operating mode

To select the operating mode, it is necessar y,

to choose the respective configuration when

creating the bus configuration. The GSD file

provides both operating modes as options.

The selection is made with the respective

configuration tool, e.g. HW-Config for SIE-

MENS S7 systems or COM PROFIBUS for

SIEMENS S5 systems.

Depending on the configuration tool, a win-

dow is opened in which the desired operat-

ing mode can be selected when adding a

VEGACOM 557 slave to the bus configura-

tion.