beautypg.com

Wiring, Warning, Observe correct ct orientation – Veris Industries E51C3 Install User Manual

Page 8: Diagram 3: 1-phase direct voltage connection 2 ct

background image

ZL0067-0C

Page 8 of 34

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E51C2, E51C3

TM

RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE

CT negative terminals are referenced to the meter’s neutral and may be at elevated voltages
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals

Failure to follow these instructions may cause injury, death or equipment damage.

WARNING

Wiring

Observe correct CT orientation.

N L1

X2

X1

White

Black

A

B

C

N

+

-

+

-

+

-

A

B

C

Diagram 1: 1-Phase Line-to-Neutral 2- Wire

System 1 CT

Diagram 2: 1-Phase Line-to-Line 2-Wire

System 1 CT

L1 L2

X2

X1

X2

X1

A

B

C

N

+

-

+

-

+

-

A

B

C

N

White

Black

White

Black

L1 L2

X2

X1

A

B

C

N

+

-

+

-

+

-

A

B

C

White

Black

Diagram 3: 1-Phase Direct Voltage Connection 2 CT

L1 L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

White

Black

White

Black

White

Black

L1

N

L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

White

Black

White

Black

White

Black

Diagram 4: 3-Phase 3-Wire 3 CT no PT

Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input

Connection 3 CT

Use System Type 11 (2L)

Use System Type 12 (2L + 1n)

Use System Type 31 (3L)

Use System Type 40 (3L + 1n)

Use System Type 10 (1L + 1n)

White

Black

White

Black

White

Black

L1

N

L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

Diagram 6: 3-Phase 4-Wire Wye Connection 3 CT

3 PT

Use System Type 40 (3L + 1n)