beautypg.com

Modbus point map (cont.) – Veris Industries E51C3 Install User Manual

Page 24

background image

ZL0067-0C

Page 24 of 34

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E51C2, E51C3

TM

E51C2 FDS

E51C3 L

og

Regist

er

R/W NV Format Units Scale

Range

Description

• 142

R/W NV UInt

%

1-99

Phase Loss Voltage Threshold in percent of system voltage (register

134). Default value is 10 (%). Any phase (as configured in register

130) whose level drops below this threshold triggers a Phase Loss

alert, i.e., if the System voltage is set to 480 V L-L, the L-N voltage

for each phase should be 277 V. When the threshold is set to 10%,

if any phase drops more than 10% below 277 V, (less than 249 V),

or if any L-L voltage drops more than 10% below 480 V (less than

432 V) the corresponding phase loss alarm bit in register 146 will

be true.

Phase Loss Output

Note: The phases tested are determined

by the System Type.

• 143

R/W NV UInt

%

1-99

Phase Loss Imbalance Threshold in Percent. Default is 25% phase

to phase difference. For a 3-phase Y (3 + N) system type (40 in

register 130), both Line to Neutral and Line to Line voltages are

tested. In a 3-phase Δ System type (31 in register 130), only Line

to Line voltages are examined. In a single split-phase (2 + N)

system type (12 in register 130), just the line to neutral voltage

are compared.

• 144

R/W NV UInt

Wh

10000,
1000,
100,
10

Wh (& VARh, if equipped)

Energy per Pulse Output

Contact Closure. If the meter

cannot find a pulse duration

that will keep up with the

max. system power (register

135), it will reject the new

value. Check the meter

configuration and/or try a

larger value.

kWh (& VARh, if equipped) Pulse Contacts

Note: The kWh pulse contact can keep up with a maximum power (Watts) of

1800000 x Wh pulse weight ÷ contact closure duration (in msec)

• 145

R

NV UInt

msec

500,
250,
100,
50,
25,
10

Pulse Contact Closure Duration

in msec. Read-only. Set to

the slowest duration that will

keep up with the theoretical

max. system power (register

135). The open time ≥ the

closure time, so the max.

pulse rate (pulses per sec)

is the inverse of double the

pulse time.

• 146

R

UInt

Error Bitmap. 1 = Active:
Bit 0: Phase A Voltage out of range
Bit 1: Phase B Voltage out of range
Bit 2: Phase C Voltage out of range
Bit 3: Phase A Current out of range
Bit 4: Phase B Current out of range
Bit 5: Phase C Current out of range
Bit 6: Frequency out of the range of 45 to 65 Hz -OR- insufficient voltage to determine frequency.
Bit 7: Reserved for future use
Bit 8: Phase Loss A
Bit 9: Phase Loss B
Bit 10: Phase Loss C
Bit 11: Low Power Factor on A with one or more phases having a PF less than 0.5 due to mis-wiring of phases
Bit 12: Low Power Factor on B
Bit 13: Low Power Factor on C
Bit 14: Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power

(registers 3 and 261/262). To fix, increase the pulse energy register (register 144) and reset the energy

accumulators (see reset register 129).

Bit 15: Energy pulse output configuration error (present pulse energy setting may not keep up with the

theoretical max. system power; see register 135). To fix, increase the pulse energy (register 144).

Modbus Point Map (cont.)