Installation Guide

Power Monitoring

E51C2, E51C3

TM

Supported System
Types

The meter has a number of different possible system wiring configurations (see Wiring Diagrams section). To configure the meter,
set the System Type via the User Interface or Modbus register 130 (if so equipped). The System Type tells the meter which of its
current and voltage inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents
unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power,
and determines which phase loss algorithm is to be used. The phase loss algorithm is configured as a percent of the Line-to-Line
System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that
have Neutral (12 & 40).

Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the Modbus registers.

CTs

Voltage Connections

System Type

Phase Loss Measurements

Wiring

Diagram

Number

of wires

Qty

ID

Qty

ID

Type

Modbus

Register 130

User Interface:

SETUP>S SYS

VLL

VLN

Balance

Diagram

number

Single-Phase Wiring
2

1

A

2

A, N

L-N

10

1L + 1n

AN

1

2

1

A

2

A, B

L-L

11

2L

AB

2

3

2

A, B

3

A, B, N

L-L with N 12

2L + 1n

AB

AN, BN

AN-BN

3

Three-Phase Wiring
3

3

A, B, C 3

A, B, C

Delta

31

3L

AB, BC, CA

AB-BC-CA

4

4

3

A, B, C 4

A, B, C, N Grounded

Wye

40

3L + 1n

AB, BC, CA

AN, BN, CN AN-BN-CN &

AB-BC-CA

5, 6

To avoid distortion, use parallel wires for control power and voltage inputs.

The following symbols are used in the wiring diagrams on the following pages.

Symbol

Description

Voltage Disconnect Switch

Fuse (installer is responsible for ensuring compliance with local requirements. No

fuses are included with the meter.)

Earth ground

X2

X1

Current Transducer

Potential Transformer

Protection containing a voltage disconnect switch with a fuse or disconnect circuit

breaker. The protection device must be rated for the available short-circuit current at

the connection point.

CAUTION

RISK OF EQUIPMENT DAMAGE

• This product is designed only for use with 1V or 0.33V current

transducers (CTs).

• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.

• Failure to follow these instructions can result in overheating and

permanent equipment damage.

Wiring Symbols