beautypg.com

Modbus point map (cont.) – Veris Industries E51C3 Install User Manual

Page 22

background image

ZL0067-0C

Page 22 of 34

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E51C2, E51C3

TM

E51C2 FDS

E51C3 L

og

Regist

er

R/W NV Format Units Scale

Range

Description

• 079

R

NV ULong

kVAh

E

0 to 0xFFFFFFFF

Accumulated Apparent Energy,

Phase A

MSR

Import

Accumulated

Apparent Energy

(Sh), Per Phase

• 080

LSR

• 081

R

NV ULong

kVAh

E

0 to 0xFFFFFFFF

Accumulated Apparent Energy,

Phase B

MSR

• 082

LSR

• 083

R

NV ULong

kVAh

E

0 to 0xFFFFFFFF

Accumulated Apparent Energy,

Phase C

MSR

• 084

LSR

• 085

R

NV ULong

kVAh

E

0 to 0xFFFFFFFF

Accumulated Apparent Energy,

Phase A

MSR

Export

• 086

LSR

• 087

R

NV ULong

kVAh

E

0 to 0xFFFFFFFF

Accumulated Apparent Energy,

Phase B

MSR

• 088

LSR

• 089

R

NV ULong

kVAh

E

0 to 0xFFFFFFFF

Accumulated Apparent Energy,

Phase C

MSR

• 090

LSR

• 091

R

SInt

kW

W

-32767 to +32767 Real Power (P), Phase A

Real Power (P)

• 092

R

SInt

kW

W

-32767 to +32767 Real Power (P), Phase B

• 093

R

SInt

kW

W

-32767 to +32767 Real Power (P), Phase C

• 094

R

SInt

kVAR

W

-32767 to +32767 Reactive Power (Q), Phase A

Reactive Power (Q)

• 095

R

SInt

kVAR

W

-32767 to +32767 Reactive Power (Q), Phase B

• 096

R

SInt

kVAR

W

-32767 to +32767 Reactive Power (Q), Phase C

• 097

R

UInt

kVA

W

0 to 32767

Apparent Power (S), Phase A

Apparent Power (S)

• 098

R

UInt

kVA

W

0 to 32767

Apparent Power (S), Phase B

• 099

R

UInt

kVA

W

0 to 32767

Apparent Power (S), Phase C

• 100

R

SInt

Ratio

0.0001 -10000 to +10000 Power Factor (PF), Phase A

Power Factor (PF)

• 101

R

SInt

Ratio

0.0001 -10000 to +10000 Power Factor (PF), Phase B

• 102

R

SInt

Ratio

0.0001 -10000 to +10000 Power Factor (PF), Phase C

• 103

R

UInt

Volt

V

0 to 32767

Voltage (U), Phase A-B

Line to Line Voltage (U)

• 104

R

UInt

Volt

V

0 to 32767

Voltage (U), Phase B-C

• 105

R

UInt

Volt

V

0 to 32767

Voltage (U), Phase A-C

• 106

R

UInt

Volt

V

0 to 32767

Voltage (V), Phase A-N

Line to Neutral Voltage (V)

• 107

R

UInt

Volt

V

0 to 32767

Voltage (V), Phase B-N

• 108

R

UInt

Volt

V

0 to 32767

Voltage (V), Phase C-N

• 109

R

UInt

Amp

I

0 to 32767

Current, Phase A

Current

• 110

R

UInt

Amp

I

0 to 32767

Current, Phase B

• 111

R

UInt

Amp

I

0 to 32767

Current, Phase C

• 112

R

UInt

Reserved, Returns 0x8000 (QNAN)

Modbus Point Map (cont.)