beautypg.com

Modbus point map (cont.) – Veris Industries E51C3 Install User Manual

Page 29

background image

ZL0067-0C

Page 29 of 34

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E51C2, E51C3

TM

Modbus Point Map (cont.)

E51C2 FDS

E51C3 L

og

Regist

er

R/W NV Format Units Scale

Range

Description

• 365/366 R

Float

kW

Real Power, Phase A

Real Power (P)

• 367/368 R

Float

kW

Real Power, Phase A

• 369/370 R

Float

kW

Real Power, Phase A

• 371/372 R

Float

kVAR

Reactive Power, Phase A

Reactive Power (Q)

• 373/374 R

Float

kVAR

Reactive Power, Phase A

• 375/376 R

Float

kVAR

Reactive Power, Phase A

• 377/378 R

Float

kVA

Apparent Power, Phase A

Apparent Power (S)

• 379/380 R

Float

kVA

Apparent Power, Phase A

• 381/382 R

Float

kVA

Apparent Power, Phase A

• 383/384 R

Float

Ratio

0.0-1.0

Power Factor, Phase A

Power Factor (PF)

• 385/386 R

Float

Ratio

0.0-1.0

Power Factor, Phase A

• 387/388 R

Float

Ratio

0.0-1.0

Power Factor, Phase A

• 389/390 R

Float

Volt

Voltage, Phase A-B

Line to Line Voltage (U)

• 391/392 R

Float

Volt

Voltage, Phase B-C

• 393/394 R

Float

Volt

Voltage, Phase A-C

• 395/396 R

Float

Volt

Voltage, Phase A-N

Line to Neutral (V)

• 397/398 R

Float

Volt

Voltage, Phase B-N

• 399/400 R

Float

Volt

Voltage, Phase C-N

• 401/402 R

Float

Amp

Current, Phase A

Current

• 403/404 R

Float

Amp

Current, Phase B

• 405/406 R

Float

Amp

Current, Phase C

• 407/408 R

Float

Reserved, Reports QNAN (0x7FC00000)

Logging Interface

• 8000

R

NV

Newest Logged Data Entry

5760 entries total (60 days at a 15 minute sub-interval)

(to)

(to)

• 13760 R

NV

Oldest Logged Data Entry

Invalid or Quiet Not A Number (QNAN) conditions are indicated by 0x8000 (negative zero) for 16 bit integers and 0x7FC00000 for 32 bit floating point numbers.

Floating point numbers are encoded per the IEEE 754 32-bit specifications.