Problem

Cause

Solution

The maintenance wrench

icon appears in the power

meter display.

There is a problem

with the inputs to the

power meter.

See the Alert sub-menu or the Diagnostic Alert Modbus Register 146

The display is blank after

applying control power

to the meter.

The meter is not

receiving adequate

power.

Verify that the meter control power are receiving the required voltage.
Verify that the heart icon is blinking.
Check the fuse.

The data displayed is

inaccurate.

Incorrect setup values

Verify the values entered for power meter setup parameters (CT and PT ratings,

system type, etc.). See the Setup section.

Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage.
Power meter is wired

improperly.

Check all CTs and PTs to verify correct connection to the same service, CT and PT

polarity, and adequate powering. See the Wiring Diagrams section for more

information.

Cannot communicate

with power meter from

a remote personal

computer.

Power meter address is

incorrect.

Verify that the meter is correctly addressed (see Setup section).

Power meter baud rate

is incorrect.

Verify that the baud rate of the meter matches that of all other devices on its

communications link (see Setup section).

Communications

lines are improperly

connected.

Verify the power meter communications connections (see the Communications

section).

Verify the terminating resistors are properly installed on both ends of a chain of units.

Units in the middle of a chain should not have a terminator.

Verify the shield ground is connected between all units.

Sign of one phase (real

power) is incorrect

CT orientation reversed

Remove CT, reverse orientation, reconnect (qualified personnel only)

Troubleshooting