beautypg.com

Modbus point map (cont.) – Veris Industries E51C3 Install User Manual

Page 27

background image

ZL0067-0C

Page 27 of 34

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E51C2, E51C3

TM

E51C2 FDS

E51C3 L

og

Regist

er

R/W NV Format Units Scale

Range

Description

• 169

R/W NV UInt

1-42,
146,
155-157,
257-336

Log Register 1 –
Default is 3 (Import Real Energy

MSR)

Log Register Selection – Write the number of the 16 bit register to be logged.

To log a 32 bit value (such as accumulators and floating point values) two

log registers must be used, one each for the most and least significant

register (MSR & LSR).

• 170

R/W NV UInt

Log Register 2 –
Default is 4 (Import Real Energy

LSR)

• 171

R/W NV UInt

Log Register 3 –
Default is 5 (Export Real Energy

MSR)

• 172

R/W NV UInt

Log Register 4 –
Default is 6 (Export Real Energy

LSR)

• 173

R/W NV UInt

Log Register 5 –
Default is 29 (Real Demand)

• 174

R/W NV UInt

Log Register 6 –
Default is 30 (Reactive

Demand)

• 175

R/W NV UInt

Log Register 7 –
Default is 31 (Apparent

Demand)

• 176

R/W NV UInt

Log Register 8 –
Default is 155 (Month/Day)

• 177

R/W NV UInt

Log Register 9 –
Default is 156 (Year/Hour)

• 178

R/W NV UInt

Log Register 10 –
Default is 157 (Minutes/

Seconds)

Floating Point Data: Summary of Active Phases

• 257/258 R

NV Float

kWh

Accumulated Real Energy: Net (Import - Export)

Accumulated Real Energy

(Ph)

Clear via register

129

• 259/260 R

NV Float

kWh

Real Energy: Quadrants 1 & 4
Import

• 261/262 R

Float

kWh

Real Energy: Quadrants 2 & 3
Export

• 263/264 R

Float

kVARh

Reactive Energy: Quadrant 1
Lags Import Real Energy (IEC) Inductive (IEEE)

Accumulated Reactive

Energy (Qh):

Quadrants 1+2= Import
Quadrants 3+4= Export

• 265/266 R

Float

kVARh

Reactive Energy: Quadrant 2
Leads Export Real Energy (IEC) Inductive (IEEE)

• 267/268 R

Float

kVARh

Reactive Energy: Quadrant 3
Lags Export Real Energy (IEC) Capacitive (IEEE)

• 269/270 R

Float

kVARh

Reactive Energy: Quadrant 4
Leads Import Real Energy (IEC) Capacitive (IEEE)

• 271/272 R

NV Float

kVAh

Apparent Energy: Net (Import - Export)

Accumulated Apparent

Energy (Sh): Import and

Export correspond with

Real Energy

• 273/274 R

NV Float

kVAh

Apparent Energy: Quadrants 1 & 4
Import

• 275/276 R

NV Float

kVAh

Apparent Energy: Quadrants 2 & 3
Export

• 277/278 R

Float

kW

Total Net Instantaneous Real (P) Power

• 279/280 R

Float

kVAR

Total Net Instantaneous Reactive (Q) Power

• 281/282 R

Float

kVA

Total Net Instantaneous Apparent (S) Power

• 283/284 R

Float

Ratio

0.0-1.0

Total Power Factor (Total kW / Total kVA)

• 285/286 R

Float

Volt

Voltage, L-L (U), average of active phases

Modbus Point Map (cont.)