F3200 Installation & Programming Manual
Document No: LT0122
Programming
Page 6-32
5 July 2001
Issue 2.7
The following table lists all of the programmable non-network parameters. The defaults
listed are for Australian operation. The previous section lists items that have defaults
specific to New Zealand operation.
Item
Options
Default
Access Codes
Qty 1-10
1 (User 0)
6 Digits
000000 (User 0)
Autotest Time
Time
9:00am
Autotest Inhibit
Dates For No Test
Stat Holidays, weekends
Autotest Alarm
Alarm Test Yes/No
No alarm test
FIP MCP Zone, Disable
Zone 1, Enabled
FFCIF Type
2/3
Type 3
FFCIF Mode
MAF Zones Only/
MAF Zones Only
All Zones/Disabled
FFCIF RZDU Remote Ack
Enabled/Disabled
Enabled
FFCIF Auto Ack
Enabled/Disabled
Disabled
FFCIF Alarm Bells
Enabled/Disabled
Disabled
FFCIF Display Cause
Enabled/Disabled
Disabled
FFCIF always flash non-maf
Enabled/Disabled
Disabled
alarm LEDs
FFCIF always send non-maf alarm
Enabled/Disabled
Disabled
to RDU
All zones isolated = Standby
Standby operate/not operate
operates
Brig Test
Operate/Not MAF Alarm Relay Operates Alm Relay (V2.07
or earlier)
No operation (V2.08 or later)
Printer
Lines Per Page
60
Baud Rate
9600
Print Relay Operates
Enabled
Event printing
Enabled
Printer and history
Event type selections for
history & printer -
- zone, system, sys run,
circuit, point, relay.
All types enabled
Coder (NSW Cty)
Disabled/1-6 Pulses
Disabled
Daylight saving start
Start time/date/diff
Last SUN, OCT, 2am, 1 hr
Daylight saving end
End time/date/diff
Last SUN, MAR, 3am, 1 hr
Mains 50/60Hz
50/60Hz
50Hz
Mains fault is fault after 8 hours
Enable/Disable
Disabled
Battery low monitor
Enable/Disable
Disabled
Battery connection monitor
Enable/Disable
Disabled
Hourly battery test
Enable/Disable
Disabled
Daily 40 minute battery test
Enable/Disable
Disabled
Charger high/low = Fault
Enable/Disable
Disabled
Alarm buzzer
Enable/Disable
Enabled
Zone fault buzzer
Enable/Disable
Enabled
System fault buzzer
Enable/Disable
Enabled
Buzzer for non-MAF zone faults
Enable/Disable
Disabled
Fault sounder after 8 hours fault
Enable/Disable
Disabled
Fault sounder after 8 hours isolate
Enable/Disable
Disabled
TABLE 6.4.1
PROGRAMMABLE PARAMETERS
Continued .......