Electrical specifications, Mains supply, Battery charger & psu – Tyco F3200 User Manual

Page 32: Electrical specifications -4, 3 electrical specifications

background image

F3200 Installation & Programming Manual

Document No: LT0122

System Specifications

Page 3-4

5 July 2001

Issue 2.7

3.3 ELECTRICAL

SPECIFICATIONS

3.3.1 MAINS

SUPPLY

Voltage

:

240Vac +6% -10%

Current

:

0.5A

Frequency

:

50Hz

Termination

:

For up to 2.5sq mm TPS

3 Way block with wire protectors

3.3.2

BATTERY CHARGER & PSU

Input Voltage

:

31Vac rms

(Transformer sec)

Charger Voltage

:

27.3Vdc (nominal at 20

°

C)

Temperature :

-36mV

per

°

C nominal

Compensation

Non-Battery Backed :

28.0 nominal

Voltage

Max Total Current

:

3Adc for std PSU (Charger, Quiescent & Alarm)

6Adc (for 6A PSU only)

Max Bell Current

:

2Adc

Max. Ancillary

:

2Adc

Current on VBF1

Max. Ancillary

:

2Adc (allows 3A max LED Display)

Current on VBF2

Max. Ancillary

:

2Adc (e.g. for door holders)

Current on VNBF

(VBF <-> battery backed, fused. VNBF <-> non-battery backed, fused)

Current Limit

Standard PSU

6A PSU

Battery to

MAF/PSU

:

PTC, 6A nom, 3.6A min

(see notes below)

PSU/Charger

:

3.3A nom, 3.0A min

6.7A nom, 6.0A min

Notes

1)

:

The 6A PSU is factory fitted in the FP0712 and FP0713. It is

not available in the FP0583.

2)

:

For the 6A PSU, the PTCs on the MAF are shorted out and a

Derwent 10A thermal cutout is wired between the battery +

terminal and the MAF/PSU.