Electrical specifications, Mains supply, Battery charger & psu – Tyco F3200 User Manual
Page 32: Electrical specifications -4, 3 electrical specifications

F3200 Installation & Programming Manual
Document No: LT0122
System Specifications
Page 3-4
5 July 2001
Issue 2.7
3.3 ELECTRICAL
SPECIFICATIONS
3.3.1 MAINS
SUPPLY
Voltage
:
240Vac +6% -10%
Current
:
0.5A
Frequency
:
50Hz
Termination
:
For up to 2.5sq mm TPS
3 Way block with wire protectors
3.3.2
BATTERY CHARGER & PSU
Input Voltage
:
31Vac rms
(Transformer sec)
Charger Voltage
:
27.3Vdc (nominal at 20
°
C)
Temperature :
-36mV
per
°
C nominal
Compensation
Non-Battery Backed :
28.0 nominal
Voltage
Max Total Current
:
3Adc for std PSU (Charger, Quiescent & Alarm)
6Adc (for 6A PSU only)
Max Bell Current
:
2Adc
Max. Ancillary
:
2Adc
Current on VBF1
Max. Ancillary
:
2Adc (allows 3A max LED Display)
Current on VBF2
Max. Ancillary
:
2Adc (e.g. for door holders)
Current on VNBF
(VBF <-> battery backed, fused. VNBF <-> non-battery backed, fused)
Current Limit
Standard PSU
6A PSU
Battery to
MAF/PSU
:
PTC, 6A nom, 3.6A min
(see notes below)
PSU/Charger
:
3.3A nom, 3.0A min
6.7A nom, 6.0A min
Notes
1)
:
The 6A PSU is factory fitted in the FP0712 and FP0713. It is
not available in the FP0583.
2)
:
For the 6A PSU, the PTCs on the MAF are shorted out and a
Derwent 10A thermal cutout is wired between the battery +
terminal and the MAF/PSU.