6 TERMINAL ISOLATED REPEATER (CONTINUED)
Programming & Limitations
All detector types require the circuit to be programmed for Mode 1 (Std) with voltage band
B1 programmed as Alarm.
The open collector must be programmed as OCn = ^ZnR, or the Relay must be programmed
as Rn = ZnR (i.e. Zone n not in Reset or Zone n in Reset respectively).
There can be no differentiation of voltage bands (B1, B2, B3) i.e. the FIP cannot differentiate
between MCP and detector operation on the same circuit.
Any alarm on the detector circuit (either a short circuit or detector operation) will cause a B1
or a B2 voltage level on the FIP AZC, depending on the battery voltage.
Detector quantity and circuit length limits are shown in Table 9.4.3.
GAS GROUP 11A OR 11B
GAS GROUP 11C
DETECTOR
CCT LENGTH
CCT LENGTH
TYPE
PART
BASE
QTY
1.0mm²
0.75mm²
QTY
1.00mm²
0.75mm²
SMOKE
C29BEx
Z94C
40(M)
3km(R)
2.2km(R)
40(M)
0.9km(C)
0.9km(C)
(100Ω)
(100Ω)
(90nF)
(90nF)
33
0.97km(C)
0.97km(C)
(97nF)
(97nF)
20
1.1km(C)
1.1km(C)
(110nF)
(110nF)
1
1.3km(C)
1.3km(C)
(130nF)
(130nF)
FLAME
R24BEx
-
7(M)
1.5km(R)
1.1km(R)
2(M)
1.2km(C)
1.1km(R)
(50Ω)
(50Ω)
(120nF)
(50Ω)
HEAT
FW105
-
-
-
-
-
1.3km TOT
1.3km TOT
(100Ω TOT)
(100Ω TOT)
(130nF)
(130nF)
40(M)
3km(R)
2.2km(R)
40(M)
1.3km(C)
1.3km(C)
HEAT
T54B
-
(100Ω)
(100Ω)
(130nF)
(130nF)
HEAT
T56B
Z500N
40(M)
3km(R)
2.2km(R)
40(M)
1.13KM(C)
1.3km(C)
(100Ω)
(100Ω)
(130nF)
(130nF)
HEAT
S231i+
-
11(M)
3KM (R)
2.2KM (R)
11(M)
1.13km(C)
1.13KM(C)
(100Ω)
(100Ω)
(113nF)
(113nF)
5
1.22km(C)
1.22km(C)
(122nF)
(122nF)
1
1.28km(C)
1.28km(C)
(128nF)
(128nF)
FLAME
S121
-
40(M)
3km(R)
2.2km(R)
32(M)
0.02km(C)
0.02km(C)
(100Ω)
(100Ω)
(2nF)
(2nF)
20
0.5km(C)
0.5km(C)
(50nF)
(50nF)
10
0.9km(C)
0.9km(C)
(90nF)
(90nF)
1
1.26km(C)
1.26km(C)
(126nF)
(126nF)
FLAME
MS302Ex
M300
40(M)
3km(R)
2.2km(R)
40(M)
0.7km(C)
0.7km(C)
(100Ω)
(100Ω)
(70nF)
(70nF)
20
1km(C)
1km(C)
(100nF)
(100nF)
1
1.28km(C)
1.28km(C)
(128nF)
(128nF)
ION
MF301Ex
M300
40(M)
(SAME AS MS302Ex)
PHOTO
MR301Ex
M300
40(M)
(SAME AS MS302Ex)
HPO
MR301TEx
M300
40(M)
(SAME AS MS302Ex)
TABLE 9.4.3
MAXIMUM DETECTOR QUANTITY & CABLE LENGTH FOR 6-TERMINAL REPEATER