Tyco F3200 User Manual
Page 157
Document No: LT0122
F3200 Installation & Programming Manual
Installation & Wiring
Issue 2.7
5 July 2001
Page 8-19
Notes
1.
Wire an in-line fuse holder with 6A fuse from Batt+.
2.
The Bell Monitor must be Rev 3 or greater and is supplied with instructions, adhesive
based stand-offs, and EOLRs.
FIGURE 8.5.6
USING BELL MONITOR BOARD ON ANCIL 3/BELLS RELAY
Batt -
NO
NC
BELLS +
0V
EOLR
+V
Evac
0V
Anc 3
Evac-
EOLR
Bell Monitor Rev 3
Up to 3 branches of
Load.
Evac+
2K7
6Adc
Fuse
Ext Def-
BELLS -
Lk2
Lk3
Lk4