Tyco F3200 User Manual
Page 163

Document No: LT0122
F3200 Installation & Programming Manual
Installation & Wiring
Issue 2.7
5 July 2001
Page 8-25
FIP FP0558 MAF CONFIGURED RDU
J11 MAF Bd connector J11
(Cut Lk1 on MAF/PSU)
┌─┐ ┌─┐
╔══════════════╡
O
│+VBF2 │
O
│+VBF2
║ ├─┤ ├─┤
║ ╔══════╡
O
│TX ╔══════════════════╡
O
│TX RZDU
║ ║ ├─┤ ║ ├─┤ COMMS
╔═══╬═══════╬══════╡
O
│0V ║ ╔═════════════╡
O
│0V
║ ║ ║ ├─┤ ║ ║ ├─┤
║ ║ ╔════╬══════╡
O
│RX ║ ║ ╔════════╡
O
│RX
║ ║ ║ ║ └─┘ ║ ║ ║ └─┘
║ ║ ║ ║ ║ ║ ║
║ ║ ║ ║ ║ ║ ║
║ ║ █════╣════════════════════╝ ║ ║
║ ║ ║ ║ ║ ║
█═══╬══╬════╬═════════════════════════╝ ║
║ ║ ║ ║ ║
║ ║ ║ █══════════════════════════════╝
║ ║ ║ ║
║ ║ ║ ║
╣ ║ ║ ║
║ ║ ║ ║
║ ║ ║ ║
║ ║ ║ ║
║ ║ ║ ║ FP0559 FP0559
║ ║ ║ ║ NON-MAF CONFIGURED RDU NON-MAF CONFIGURED RDU
║ ║ ║ ║ EXTERNALLY POWERED
║ ║ ║ ║ Ext 24V PSU (Cut Lk3 on Remote Term)
║ ║ ║ ║ ┌─┐+24V ║ ║ ┌─┐ ──┐
║ ╚══╬════╬══════╡
O
│ ║ ╚═══════════╡
O
│+24V │
║ ║ ║ ├─┤0V ║ ├─┤ │
║ ║ ║ │
O
│ ╚══════════════╡
O
│0V ──┘
║ ║ ║ ├─┤0V ├─┤
╚══════║════║══════╡
O
╞══════════════════════════════╡
O
│0V ──┐
║ ║ ├─┤RX ├─┤ │RZDU
║ ╚══════╡
O
╞══════════════════════════════╡
O
│RX │COMMS
║ ├─┤TX ├─┤ │
╚═══════════╡
O
╞══════════════════════════════╡
O
│TX ──┘
└─┘ └─┘
Connectors J1 & 2, Remote Termination Bd
FIG 8.8.1
EXAMPLE OF RDU COMS WIRING