Maf/psu inputs – Tyco F3200 User Manual
Page 40

F3200 Installation & Programming Manual
Document No: LT0122
System Specifications
Page 3-12
5 July 2001
Issue 2.7
AZC SPECIFICATIONS (CONTINUED)
Timing
Standard Delay
2.3 sec (2.0 - 2.6 sec)
(into Alarm, Fault, Normal)
AZC Reset
5.3 sec (5.0 - 5.6 sec)
AZC Ignore Period 1
2 sec nom (plus std 2.3 sec delay)
(after Reset)
AZC Ignore Period 2
1 sec nom (plus std 2.3 sec delay)
(after Start Up or Programming)
AZC Time Into Alarm
Programmable 0-250 sec
AZC Time Out of Alarm
Programmable 0-250 sec
Refer to Section 7.2.4 for detail on other sequences and programmable delays.
3.4.2 MAF/PSU
INPUTS
Battery Termination
One pair screw terminals; 4sq mm max cable
AC Input
31V rms; 3.6A rms; 2.8mm tab terminals
Door Switch
5V, 0.5mA, Unsupervised, 4 Way .1" pcb header, J6
MCP
5V, 1mA, 2k7 EOLR, 4 Way .1" pcb header, J6
Spare Inputs (not fitted)
5V, 0.5mA, Unsupervised, Cabinet internal use only, 4 Way
.1" pcb header, J5
Relay Supervision
Anc 1 Sup/Anc 2 Sup
One screw terminal each
Modes of Operation
1 Door holder (Default for Anc 1)
2 Load (Default for Anc 2)
Relay Off
Relay On
Door Holder Mode expects
Voltage Present
No Voltage Present
Load mode expects
Resistive to 0V
Open Circuit or Voltage Present
Voltage Threshold
3.65V Nom
(Door Holder Mode)
Supervision Current
0mA @ +5V, 1mA @ 0V
Load Resistance
400 Ohm - 10k Ohm
(Load Mode)
less than 400 Ohm with series diode at load.
14 Ohm absolute minimum.
Bells Relay
Form
Reverse polarity - requires series diode at each device