Output specifications, 8 zone module outputs, 8 relay module outputs – Tyco F3200 User Manual
Page 42: Output specifications -14, 5 output specifications

F3200 Installation & Programming Manual
Document No: LT0122
System Specifications
Page 3-14
5 July 2001
Issue 2.7
3.5 OUTPUT
SPECIFICATIONS
3.5.1
8 ZONE MODULE OUTPUTS
Type
Darlington open collector
Switch to 0V
Voltage Rating
28.5V max, "off" state
1V max @ 30mA, "on" state
1.1V max at 100mA
Current Rating
100mA max per O/P, 0.6A max per module
1A max per FIP.
Transient Protection
Allows external wiring
Terminations
8 Way demountable screw terminal
1.5sq mm max. cable
Operation
Programmable
Default
O/C 1 = Zone 1 Alarm
O/C 2 = Zone 2 Alarm
etc.
3.5.2
8 RELAY MODULE OUTPUTS
Form
1 Pole changeover contacts
Voltage-free when unsupervised
Termination
Demountable screw terminals
1.5sq mm max cable
Rating
ELV only
30V, 2Adc resistive
30V, 1Adc inductive
Note
The relays are 2 pole, with the second pole terminated on pcb pads.
Operation
Programmable
Supervision
Ref 3.4.4.
Looping Terminals
2 Sets of 4 joined
voltage-free terminals per module