MAF/PSU INPUTS (CONTINUED)
End of Line Resistor
No. of Circuits
Type
1
3k3, 5%, 250mW resistor
2
6k8, 5%, 250mW resistor
3
10k, 5%, 250mW resistor
Supervision Current
0mA @ +5V, 1.5mA @ 0V, +ve to BELLS- terminal
Circuit Resistance
100 Ohm max.
3.4.3 CONTROLLER/DISPLAY
INPUTS
Spare DC Input/Output
24Vdc nom demountable screw terminal, 4 way, J5
Spare Input
22V, 10k Ohm pull up resistor
Provision for supervision (up to 5 band)
Spare Inputs IP0, 1, 2
Unsupervised, Cabinet internal use only
(not fitted)
+5V, 100k pull up resistor, 10 Way FRC header, J10
Serial I/O
RZDU Refer Section 3.5.3; Others 3.5.2
3.4.4
8 RELAY MODULE SUPERVISION
Form
Load monitoring
Relay Off
Relay On
Expects
Resistance to 0V
Voltage Present
Selected By
Minijump link on pcb & programming of FIP
Default Programming
Disabled (unsupervised)
Load Resistance
400 Ohm - 10k Ohm
Less than 400 Ohm with series diode at load
14 Ohm absolute minimum
Voltage Threshold
3.65V nom.
Supervision Current
0mA @ +5V, 1mA @ 0V
3.4.5
NZ MODE DISPLAY EXTENDER BOARD INPUTS
The Display Extender Board is used with New Zealand operation only. The inputs it
provides are : Silence Alarms, Trial Evac, Building Services Restore, Lamp Test and
External Defect. All inputs have closure to zero volts to assert the input. An input may be
left open or unconnected if not used. Refer to section 12.8 for wiring.
All Inputs
Closure below 1.5V @ 0.35mA required to activate.
Open voltage = 5V