MAF/PSU INPUTS (CONTINUED)

End of Line Resistor

No. of Circuits

Type

1

3k3, 5%, 250mW resistor

2

6k8, 5%, 250mW resistor

3

10k, 5%, 250mW resistor

Supervision Current

0mA @ +5V, 1.5mA @ 0V, +ve to BELLS- terminal

Circuit Resistance

100 Ohm max.

3.4.3 CONTROLLER/DISPLAY

INPUTS

Spare DC Input/Output

24Vdc nom demountable screw terminal, 4 way, J5

Spare Input

22V, 10k Ohm pull up resistor

Provision for supervision (up to 5 band)

Spare Inputs IP0, 1, 2

Unsupervised, Cabinet internal use only

(not fitted)

+5V, 100k pull up resistor, 10 Way FRC header, J10

Serial I/O

RZDU Refer Section 3.5.3; Others 3.5.2

3.4.4

8 RELAY MODULE SUPERVISION

Form

Load monitoring

Relay Off

Relay On

Expects

Resistance to 0V

Voltage Present

Selected By

Minijump link on pcb & programming of FIP

Default Programming

Disabled (unsupervised)

Load Resistance

400 Ohm - 10k Ohm

Less than 400 Ohm with series diode at load

14 Ohm absolute minimum

Voltage Threshold

3.65V nom.

Supervision Current

0mA @ +5V, 1mA @ 0V

3.4.5

NZ MODE DISPLAY EXTENDER BOARD INPUTS

The Display Extender Board is used with New Zealand operation only. The inputs it
provides are : Silence Alarms, Trial Evac, Building Services Restore, Lamp Test and
External Defect. All inputs have closure to zero volts to assert the input. An input may be
left open or unconnected if not used. Refer to section 12.8 for wiring.

All Inputs

Closure below 1.5V @ 0.35mA required to activate.
Open voltage = 5V