F3200 Installation & Programming Manual

Document No: LT0122

Installation & Wiring

Page 8-24

5 July 2001

Issue 2.7

8.9

RDU

WIRING

A FIP may drive up to 8 Remote Display Units (RDUs) that are programmed to send

information back to the FIP. More "monitoring only" devices may be connected to the FIP

RZDU Tx line. Some RDUs have their own power, but others require their power (24Vdc) to

be supplied from the FIP or an approved PSU with battery backup.

The RDUs are all connected in parallel on common Tx and Rx circuits. Star and Bus wiring

connections are permitted as shown in Fig 8.8.1.

NOTE: TX from the FIP goes to RX on ALL RDUs

RX from the FIP goes to TX on ALL RDUs

Fig 8.8.1 shows an example of interconnection between both MAF and Non-MAF configured

RDU(s) and the FIP.

NOTES:

To maintain electrical isolation:

(1)

Lk1 on the MAF/PSU Board should be cut for RDUs with their own

MAF/PSU module.

(2)

Non-MAF configured RDUs that are powered by a PSU other than the

FIP must have Lk3 on the Remote Termination Board cut and Lk14 on

the Controller in the “R” position.

Cable Limitations

The maximum distance to the furthest RDU is determined by the cable type used and the

wiring arrangement.

(1)

The MAXIMUM line resistance loop (FIP TX out, 0V return must not be greater than

150 Ω.

(2)

The MAXIMUM inter-wire capacitance at the FIP RZDU terminals MUST NOT

exceed 100 nF. This must be the total of all cables used - not just the length to the

furthest RDU. Typically this is 1km of TPS cabling.

(3)

The +V and 0V cables must be of sufficient size to avoid excessive voltage drops to

RDUs when they are drawing maximum current (e.g. lamp test).