Maf/psu outputs – Tyco F3200 User Manual
Page 43

Document No: LT0122
F3200 Installation & Programming Manual
System Specifications
Issue 2.7
5 July 2001
Page 3-15
3.5.3 MAF/PSU
OUTPUTS
Brigade Relays
Number
4
Standby
Normally energised
De-energises on battery fail or panel fail
Fault, Isolated, Alarm
Normally de-energised
Energise on active state
Form
1 Pole changeover contacts
Voltage-free
Termination
Demountable screw terminals
1.5sq mm max cable
Rating
ELV only
30V, 5Adc resistive
30V, 3Adc inductive
Isolation
1500V rms contact to coil
Ancillary & Bells
Number
3
Anc 1, Anc 2
1 Pole changeover contacts
Voltage-free
Termination
Demountable screw terminals
1.5sq mm max cable
Rating
ELV only
30V, 2Adc resistive
30V, 1Adc inductive
(Note: The relays are 2 pole, with second pole terminated on pcb pads).
Operation
Programmable
Default
Active on any unisolated Zone Alarm.
Supervision
Separate terminal (ref 3.4.2)
Anc 3/Bells
2 pole relay
Link selectable function
Standard Format
Bells
Switched 24Vdc output
2 terminals, Bells +, -
Demountable screw terminals
1.5sq mm max cable