beautypg.com

Battery/charger calculations – Tyco F3200 User Manual

Page 58

background image

F3200 Installation & Programming Manual

Document No: LT0122

Configuring a FIP

Page 5-4

5 July 2001

Issue 2.7

GENERAL (CONTINUED)

4.

The approvals laboratory recommends using 90% derating of batteries used on

F3200 because the battery fail voltage (Standby) is 22V instead of 21V (as used on

some other FIPs). The local approval body may not require this, however, because

although the F3200 will not generate new alarms below the "battery fail voltage", it

will maintain any alarms and outputs that occurred when the voltage was higher than

the battery fail voltage. AS1670.1 1995 does, however, recommend 80% derating of

batteries for the effect of ageing, ie. multiply the required battery capacity (at end of

life) by 1.25 when calculating the required capacity for a new battery.

5.

For maximum physical battery sizes refer to "Battery Size". (Refer to Section 5.3.4).

5.3.2 BATTERY/CHARGER

CALCULATIONS

The recommended order of calculations is as follows:

1.

Calculate the FIP quiescent load (Iq) from the figures given in Section 3.3.5. Note

that the detector load for each AZC has to be added to the quiescent current per

AZC. Calculate In separately, where In is the external non-alarm, non-battery

backed load on the FIP PSU (e.g. door holders).

2.

Calculate the FIP alarm load (Ia) for 2 zones in alarm from Section 3.3.5. (Include all

external loads e.g. bells, relays).

3.

Calculate the 5 hour/0.5 hour battery capacity for the charger requirement as follows:

Cap (5 hr) = (5 x Iq) + (0.5 Ia x 1.33) Ahr

= 5Iq + 0.66Ia where

Iq = quiescent current

Ia = alarm current

Note that the 1.33 multiplier increases the required capacity to allow for an alarm

load of up to 10 times the quiescent load (i.e. 75% derating of capacity).

4.

Find the greater of Iq + In, or Ia. Calculate the power supply/charger requirement (Ic)

as follows and check that it is less than 3A. (If greater a 6A charger is required).

Ic = I + Cap (5 hr)

÷

24e where I is the greater of Iq + In, or Ia, and e is the changing

efficiency of the particular battery being used, at the current being used (typically

80%, ie. (cap/24) x 1.25).

5.

Calculate the battery capacity as follows:

Cap (24 hr) = (24 x Iq + 0.66 Ia) x 1.25

(See note 4 of Section 5.3.1 regarding the x 1.25 multiplier).

Select a battery which has a rated capacity (i.e. 20 hr rating) equal to or above that

just calculated. (Refer to Sections 3.3.3 and 5.3.4 for approved types).