Tyco F3200 User Manual
Page 178

F3200 Installation & Programming Manual
Document No: LT0122
Applications
Page 9-10
5 July 2001
Issue 2.7
LOGIC & CONFIGURATION (CONTINUED)
Relay 1 = Alert O/P (1st stage sign FIRE ALARM)
Relay 2 = Evac O/P (2nd stage sign EVACUATE and DO NOT ENTER)
Relay 3 = Gas Release Solenoid
Relay 4 = System Inoperative sign
Isolate = Guard Relay (see note 2)
Timer
T1 [S30:0] = V1
30 Second time delay from "Gas Initiated" (second stage).
Variables
V1 = Z1A.Z2A.^Z5A + Z3A
Open Collector LEDs
OC1 = V1
OC2 = Z3A
OC3 = Z4A
OC4 = Z5A + OC5 + Z7A + Z4:7(1)I + Z1:7(1)F + R3F +R1I+R2I +R4I (see notes 2,9)
OC5 = Z6A+Z1:3(1)I + R3I + Guard Iso (if isolatable, see note 2)
Relays
R1 = Z1A + Z2A + Z3A + Z4A
(Alert)
R2 = Z4A + V1
(Evac)
R3 = T1
(Gas Release)
R4 = OC4
(System Inoperative)
ISO (or Rn) = V1
(Guard) (see note 2)
Configure Circuits
AZC
Alarm Text
B1
Circuit 1
Smoke (1)
-
Circuit 2
Smoke (1)
-
Gas Start
MCP/Manual (4)
-
Gas Released
FSW (3) or PSW (6)
Alarm (2)
Gas Inhibit
MCP/Manual (4)
-
Gas Isolated
MCP/Manual (4)
If required (see note 3)
Lock-off Valve
VMD/Valve (5)
If required (see note 9)
(Circuits 1 and 2 use all default settings).
Configure Zones
Zone
Latch MAF Anc1 Anc2 Bells
Circuit 1
-
-
- - -
Circuit 2
- -
- - -
Gas Start
N ? -
- - - (see note 10)
Gas Released
- -
- - -
Gas Inhibit
N N N N N
Gas Isolated
N N N N N If required (see note 3)
Lock-off Valve
N
N
N
N
N If required (see note 9)
(Zones 1-4 use all default settings. Zone 3 may be required to be non-latching. See note 10.)