F3200 Installation & Programming Manual

Document No: LT0122

System Specifications

Page 3-8

5 July 2001

Issue 2.7

3.4 INPUT

SPECIFICATIONS

3.4.1 AZC

SPECIFICATIONS

General

Terminations

On 8 Zone Module, 2 per AZC.

Demountable screw terminal 1.5sq mm cable max.

Number

8 AZCs per 8 Zone Module.

64 max per system.

End of Lines (EOLs)

Mode

EOL

1 Standard

2k7, 5%, 400mW resistor

2 High Current

2k7, 5%, 400mW resistor

3 Low Current

10k, 5%, 400mW resistor

4 Tamper

EOL002B active EOL

5 Disabled

None

Circuit Resistance & Capacitance

Mode

Capacitance

Resistance

1, 2 & 4

500nF

50 Ohm max

3

1000nF

800 Ohm max for B2 Alarm

2k Ohm max for B3 Alarm

Voltages

Min

Typ

Max

Detector Supply

on MAF/PSU (note 1)

21.2V

22.0V 22.2V

(21.8V)

at AZC terminals

18.75V

20.3V 22.1V

at end of circuit

18.0V

20.3V 22.1V

Alarm Voltage Thresholds

Band B3 upper threshold

17.2V

17.5V 17.8V

Band B3 lower threshold

12.75V

13.1V 13.45V

Band B2 upper threshold

Band B2 lower threshold

2.7V

2.9V

3.1V

Band B1 upper threshold

Band B1 lower threshold

0V

0V

0V