F3200 Installation & Programming Manual
Document No: LT0122
Programming System Configuration
Page 7-10
5 July 2001
Issue 2.7
VOLTAGE BANDS (CONTINUED)
Voltage bands and their interpretation for modes 1, 2 and 3 are shown in Table 7.2.1
following.
Band Voltage
Status
Default Status
B5
21-22VFault (Open Circuit)
Fault (Open Circuit)
B4
17.5-21V
Normal
Normal
B3
13-17.5V
Programmable
Normal (V1.XX software)
Instant alarm (V2.XX software)
B2
3-13V
Alarm Alarm
(Detector Operated) (Detector Operated)
B1
0-3V
Programmable
Instant Alarm (Manual)
TABLE 7.2.1
AZC VOLTAGE BANDS FOR MODES 1-3
In Mode 4, for AZC normal the voltage is in B5 with pulses into B4 due to the active end-of-
line device. B2 is Alarm (valve operated). B3 is programmable to Alarm or Fault only
(default is Alarm). B1 is programmable (default is Fault). All other conditions are Fault
(Tamper).