F3200 Installation & Programming Manual

Document No: LT0122

Programming System Configuration

Page 7-10

5 July 2001

Issue 2.7

VOLTAGE BANDS (CONTINUED)

Voltage bands and their interpretation for modes 1, 2 and 3 are shown in Table 7.2.1

following.

Band Voltage

Status

Default Status

B5

21-22VFault (Open Circuit)

Fault (Open Circuit)

B4

17.5-21V

Normal

Normal

B3

13-17.5V

Programmable

Normal (V1.XX software)

Instant alarm (V2.XX software)

B2

3-13V

Alarm Alarm

(Detector Operated) (Detector Operated)

B1

0-3V

Programmable

Instant Alarm (Manual)

TABLE 7.2.1

AZC VOLTAGE BANDS FOR MODES 1-3

In Mode 4, for AZC normal the voltage is in B5 with pulses into B4 due to the active end-of-

line device. B2 is Alarm (valve operated). B3 is programmable to Alarm or Fault only

(default is Alarm). B1 is programmable (default is Fault). All other conditions are Fault

(Tamper).