Detailed explanations on the auxiliary area, Error codes and error flags, 359 auxiliary area allocations appendix d – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual
Page 382

359
Auxiliary Area Allocations
Appendix D
Detailed Explanations on the Auxiliary Area
Error Log Area: A100 to A199
Error Codes and Error Flags
Note
(1) Codes C101 to C2FF will be stored for FALS numbers 001 to 511.
(2) Codes 4101 to 42FF will be stored for FAL numbers 001 to 511.
(3) Only the contents of A405 is stored as the error flag contents for program errors.
(4) 0000 hex will be stored as the error flag contents.
0101
0101
0101
0101
0101
0101
A100
A101
A102
A103
A104
A195
A196
A197
A198
A199
01 01
01 01
01 01
80 F1
00 04
01 01
01 01
01 01
C1 01
00 00
Error code
Error contents
Error code
Error contents
Error
record
Error
record
The following data would be generated in an error record if
a memory error (error code 80F1) occurred with the error
located in the System Setup (04 hex).
The following data would be generated in an error record if
an FALS error with FALS number 001 occurred
Classification
Error code
Meaning
Error flags
System-defined
fatal errors
80F1
Memory error
A403
80C0
I/O bus error
---
80CE
No End Cover
---
80CF
Sync bus error
80E0
I/O setting error
---
80F0
Program error
A405
809F
Cycle time too long error
---
System-defined
non-fatal errors
009B
System Setup setting error
A409
User-defined
fatal errors
C101 to C2FF
FALS instruction executed (See note 1.)
---
User-defined
non-fatal errors
4101 to 42FF
FAL instruction executed (See note 2.)
---