System Setup, Auxiliary Area Allocations, and Built-in I/O Allocations
Appendix C
CX-Programmer: Analog Input/Output Tab Page
Note Analog outputs that are not being used can be disabled to decrease the cycle time.
Details on System Setup Settings
Startup Mode
This setting determines the operating mode that will be used when the power supply to the Coordinator Module
is turned ON.
Note The Coordinator Module will start in RUN mode unless the Startup Mode setting in the System Setup is
enabled.
Peripheral Port Settings
The standard settings are for Host Link Mode, 1 start bit, 7-bit data, even parity, 2 stop bits, and 9,600 baud.
Change the System Setup if any other settings are required.
RS-232C Port Settings (Host Link Port)
The standard settings are for Host Link Mode, 1 start bit, 7-bit data, even parity, 2 stop bits, and 9,600 baud.
Change the System Setup if any other settings are required. If no-protocol communications are to be used, be
sure to change the frame format.
+330 to 331 00 to 15 High-speed
counter 1 (Counter
1)
Absolute offset
8000 0000 to 7FFF FFFF hex
Application origin when using an absolute encoder.
Immediately
+332 to 333 00 to 15 High-speed
counter 2 (Counter
2)
Absolute offset
Same as high-speed counter 1.
Address
Bits
Function
Remarks
When setting is read
+350
00 to 03 Analog I/O
Input method
0 hex: END refresh
1 hex: Immediate refresh (using PRV(881)
instruction)
At power ON
04 to 07
Output method
0 hex: END refresh (Analog value output to
A560 and A561 after executing END(001).)
1 hex: Immediate refresh (using instructions)
(Analog value output when SPED(885) or
ACC(888) is executed.) (A560 and A561 are
used for monitoring.)
+351
00 to 07 Analog input
Input range
00 hex:
−10 to 10 V
01 hex: 0 to 10 V
02 hex: 1 to 5 V (4 to 20 mA)
03 hex: 0 to 5 V
At power ON
+353
00 to 07 Analog output 1
Output range
00 hex:
−10 to 10 V
01 hex: 0 to 10 V
02 hex: 1 to 5 V
03 hex: 0 to 5 V
5A hex: Output disabled (Can be used to
shorten I/O refresh time.) (See note.)
At power ON
08 to 11
Output stop func-
tion
0 hex: Clear
1 hex: Hold
2 hex: Maximum value
+354
00 to 07 Analog output 2
Output range
Same as for analog output 1.
08 to 15
Output stop func-
tion
System Setup mode setting disabled
RUN mode
System Setup mode setting enabled
Program: PROGRAM mode
Monitor: MONITOR mode
Run:
RUN mode
Address
Bits
Function
Remarks
When setting