Module i/o refresh times, 291 programming appendix a – Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-MMA21 User Manual
Page 314
291
Programming
Appendix A
4.
I/O Refreshing
5.
Cyclic Refreshing
6.
Sync Bus Refreshing
7.
Peripheral Service
Module I/O Refresh Times
Cyclic Refresh Time in the Coordinator Module
Cyclic Refresh Time in Motion Control Modules
Details
Processing time and fluctuation cause
The built-in I/O and special inputs (pulse/analog) on the
Motion Control Module are refreshed.
MMP21: 48
µs
MMA21: 135
µs
Motion Control Module I/O refresh time
Details
Processing time and fluctuation cause
Cyclic refresh with the Coordinator Module
21
µs
Details
Processing time and fluctuation cause
The sync bus between the Coordinator Module and
Motion Control Modules is refreshed.
60
µs
Details
Processing time and fluctuation cause
Event servicing with Motion Con-
trol Modules
40
µs + Event service time
Event service time includes event servicing for DM area transfers requested by
the Coordinator Module, event processing for requests from the CX-Program-
mer, etc.
Model
I/O refresh time
FQM1-MMP21/MMA21
40
µs per Module
Model
I/O refresh time
FQM1-MMP21/MMA21
21
µs