Melsec-q, 4 settings and procedures prior to operation – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 97

background image

4 - 16 4 - 16

MELSEC-Q

4 SETTINGS AND PROCEDURES PRIOR TO OPERATION

(b) Communication rate setting (CH1 side: switch 1 (upper level); CH2 side:

switch 3 (upper level)) 1 2 3

Bit position

Bit position

Communication rate

(Unit: bps)

b15 to b8

Communication rate

(Unit: bps)

b15 to b8

Remarks

50

0F

H

14400

06

H

300

00

H

19200

07

H

600

01

H

28800

08

H

1200

02

H

38400

09

H

2400

03

H

57600

0A

H

4800

04

H

115200

0B

H

9600

05

H

230400

0C

H

Try lowering the communication

rate when data cannot be

communicated normally with an

external device due to overrun

errors and framing errors etc.

1 Transmission speed of 230,400 bps is available for only CH1 of the

QJ71C24N (-R2/R4).

2 When connecting external devices to both of two interfaces, the total of

the communication speed should be 115,200bps or less (230,400 bps

or less if using QJ71C24N (-R2/R4)). When connecting an external

device to either of two interfaces, the maximum of 115,200 bps is

available for the interface (the maximum of 230,400 bps if using

QJ71C24N (-R2/R4)). In this case, set 300 bps for the other interface to

which no external device is connected.

3 Set "00

H

" to the interface for which "GX Developer connection" is set in

the communication protocol setting. Serial communication module will

operate at the communication speed set on the GX Developer.

(c) Communication protocol setting (CH1 side: switch 2; CH2 side: switch 4)

Set number

Description

Remarks

0

H

GX Developer connection

GX Developer communication rate and transmission specifications are

automatically set.

1

H

Format 1

2

H

Format 2

3

H

Format 3

4

H

Format 4

For communication with ASCII code in the specified form of an A compatible 1C

frame or QnA compatible 2C/3C/4C frame

5

H

MC protocol

Format 5

For communication with binary code in a QnA compatible 4C frame

6

H

Non procedure protocol

For communication using non procedure protocol

7

H

Bidirectional protocol

For communication using bidirectional protocol

8

H

For linked operation setting

Set to the CH1 side when CH1 and CH2 interfaces are used in linked operation

(operated with the communication protocol of the CH2 side).

9

H

to D

H

Setting prohibited

E

H

ROM/RAM/switch test

For self-diagnosis of the modules

F

H

Individual station loopback test

For checking operation of each interface of the modules