4 - 9 4 - 9

MELSEC-Q

4 SETTINGS AND PROCEDURES PRIOR TO OPERATION

(c) Terminal resistor must be set (or connected) for the station of both ends on

the circuit.

Match the Q series C24 to the specifications of the external device and

connect a terminal resistor (packed with the Q series C24) according to this

section.

Connect, or set a terminal resistor at the external device according to the

instruction manual of the external device.

(The terminal resistor to connect to the Q series C24)

• When communications performed using RS-422, "330

1/4 W" resistor is

connected.

• When communications performed using RS-485, "110

1/2 W" resistor is

connected.

How to discriminate between the terminating resistors

330

110

Brown

Orange Orange

Brown Brown

Brown

(d) If data cannot be communicated with the external device at all, the polarity of

the external device could be wrong and should be checked again. If the

polarities of the Q series C24 and the external device do not match, reverse

the polarity of each signal on either device side and connect the devices with

the cable; this may enable the data to be communicated.

POINT

(1) For terminal resistor setting/connection described in this section, when the RS-

232 to RS-422 converters or similar device is used at the external device at

both ends of the circuit, a terminal resistor must be set, or connected, at the

converter.

(2) When using the RS-232C to RS-422 converters to connect the external

devices and the Q series C24, use a converter that is compatible with the

external device and PLC CPU system configuration (1:1, 1:n, m:n).

(3) Device connected to the Q series C24 RS-422/485 interface must be

standardized as RS-422 or RS-485, including 1:n and m:n connections.

(2) Connection examples

(a) External device and Q series C24 with 1:1 system configuration

Terminal
resistor

R

R

Q series C24

Signal name

SDA

SDB

RDA

RDB

External device

RDA

RDB

SDA

SDB

RSA

RSB

CSA

CSB

SG

FG

SG

FG

FG