10 - 31 10 - 31

MELSEC-Q

10 TROUBLESHOOTING

10.3.3 Troubleshooting when the Q series C24 does not return a response message even

though an external device transmitted a message and the "RD" LED blinked

Symptom

Cause

Corrective action

MC

Bidi

rectio

nal

No

n

procedure

• Communication protocol

is set incorrectly.

• Check if the communication protocol is set

correctly.

• Check if the mode was switched without using

the buffer memory mode switching area.

Note

• The communication protocol setting contents

and the communication protocol in the current
operation can be checked at buffer memory
addresses 250

H

to (CH1) and 260

H

(CH2).

• When "Check CD

terminal" was set, the CD

terminal was turned OFF.

• Since the message is initialized (skipped reading)

when the CD terminal is turned OFF when "Check
CD terminal" is set, change the wiring so that the
CD terminal remains on all the time.

• The header byte of the

message is not data

needed by the set

protocol and format.

• Check if the external device sent a message

matched to the protocol and format.

Note

• The Q series C24 skips all the messages

transmitted until the header byte set for each
protocol and format (for example, "ENQ
(05

H

)" for format 1) is received.

• The Q series C24

station No. switch

setting and message

station No. designation

do not match.

• Check the Q series C24 station No. setting and

message station No. designation.

Note

• When the station No. designation is local

station after the header byte set for each
protocol and format is received, the Q series
C24 performs receive processing.

• The Q series C24 data

communications

monitoring time is set to

"infinite", or the

monitoring time is too

long.

• Set, or shorten, the monitoring time and

retransmit the message from the external
device and determine the trouble from the
contents of the time-out error.

Note

• Error detection by watchdog timers (timer 0 to

timer 2) is possible in the following cases.
• When part of a message is skipped.
• When transmission from an external device

is interrupted.

• When a link error was generated while

accessing another station over a
MELSECNET/H, MELSECNET/10.

See Chapter 6 of User's Manual (Application)
for a detailed description of the monitoring time.

• An external device

transmitted a message

and "RD" blinked, but

the Q series C24 did

not return a response

message. ("NEU"

remains on and "SD"

does not blink)

• The path setting of the

PLC CPU to be

accessed is incorrect.

Check the path of the PLC CPU to be accessed

and set the path again.