Appendix 9.6 When clearing received data

The following program example uses the receive data clear request area of the buffer

memory.

Refer to Section 6.1.4 for received data clear.

(1) Program conditions

The following program clears the received data in the OS area of the QJ71C24N

when the receive clear command (X1025) turns ON.
(a) Devices used

:

• Receive clear command ......................................................... X1025

• Receive clear processing execution command ..................... M10

• Receive processing flag.......................................................... M11

• Transmission processing flag................................................. M12

• Receive clear command pulse signal .................................... M15

• Receive clear acceptance flag ............................................... M16

• Receive clearing flag............................................................... M17

• Communication disable flag ................................................... M18

• Communication enable flag .................................................... M19

• Completion check flag ............................................................ M20

• Receive clear processing execution status acquisition

command ................................................................................ M21

• Receive clear processing execution status judgment

command ................................................................................ M22

• Completion device for REMFR/REMTO instruction .............. M100 to 103

• Normal/abnormal completion flag for REMFR/REMTO

instruction................................................................................ M200, M201

• Receive data clear request area information ......................... D0

• Clear request........................................................................... D1

(b) Intelligent function module switch settings (Refer to Section 4.5.2)

Bit

Switch No.

Position

Designated value

Description

Setting

value

b0

OFF

Operation setting

Independent

b1

OFF

Data bit

7 bits

b2

OFF

Parity bit

No

b3

OFF

Even/odd parity

Odd

b4

OFF

Stop bit

1 bit

b5

OFF

Sum check code

No

b6

ON

Write during RUN

Enabled

b7

ON

Transmission

setting

Setting modifications

Enabled

Switch 1

b8 to b15

Communication rate setting

19200bps

07C0

H

Switch 2

Communication protocol setting

Non-procedure protocol

0006

H

Switch 5

Station number setting

Station 0

0000

H

(c) Buffer memory settings used in this example

Address Decimal (Hexadecimal)

CH1

Name

Setting

value

168 (A8

H

)

Receive data clear request

0, 1