Melsec-q, 3 specifications – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 79

background image

3 - 29 3 - 29

MELSEC-Q

3 SPECIFICATIONS

Address

Decimal (Hex)

Applicable

protocol

CH1

CH2

Application

Name

Initial

value

MC Non

Bi

Registration

allowed/not

allowed

Reference

section

8422

(20E6

H

)

8678

(21E6

H

)

Transmission pointer designation (for condition

agreement transmission)

1 to 100: Output head point (send from nth)

Send the user frames designated in the following

transmission frame No. designation areas from the

designated pointer position.

(address: CH1 side = BA

H

to 11D

H

, CH2 side =

15A

H

to 1BD

H

)

Output count designation (for condition agreement

transmission)

8423

(20E7

H

)

8679

(21E7

H

)

1 to 100: Output count (designate the number of

frame transmissions)

Data No. for connection designation (for condition

agreement transmission and notification)

8424

(20E8

H

)

8680

(21E8

H

)

For designation

of PLC CPU

monitoring

function

CPU

abnormal

monitoring

designation

0BB8

H

to 0BD5

H

, 8001

H

to 801F

H

: Data No. for

connection

0

R

Allowed

Chapter 2

of User's

Manual

(Application)

8425 to

8447

(20E9

H

to

20FF

H

)

8681 to

8703

(21E9

H

to

21FF

H

)

Use prohibited

System area

8448 (2100

H

)

Use Prohibited

System area

8449 (2101

H

)

Data No. for callback designation 1
0BB8

H

to 0BD5

H

, 8001

H

to 801F

H

: Data number for callback.

8450 (2102

H

)

Data No. for callback designation 2

8451 (2103

H

)

Data No. for callback designation 3

8452 (2104

H

)

Data No. for callback designation 4

8453 (2105

H

)

Data No. for callback designation 5

8454 (2106

H

)

Data No. for callback designation 6

8455 (2107

H

)

Data No. for callback designation 7

8456 (2108

H

)

Data No. for callback designation 8

8457 (2109

H

)

Data No. for callback designation 9

8458 (210A

H

)

For callback
function

Data No. for callback designation 10

0

RW

Allowed

Section

8.4.4

Chapter 3 of

User’s

Manual

(Application)

8704 to

8707

(2200

H

to

2203

H

)

8960 to

8963

(2300

H

to

2303

H

)

Use prohibited

System area

8708

(2204

H

)

8964

(2304

H

)

PLC CPU monitoring function operation status

0: Not executed (waiting for registration of PLC CPU monitoring)

1: Wait for PLC CPU monitoring time

(waiting to access PLC CPU)

2: Accessing PLC CPU

3: Sending monitoring results

PLC CPU monitoring function execution result (current)

8709

(2205

H

)

8965

(2305

H

)

0: Normal completion

1 or more: Abnormal completion (error code)

PLC CPU monitoring function number of transmission

8710

(2206

H

)

8966

(2306

H

)

0: Not executed

1 or more: Number of transmissions

8711

(2207

H

)

8967

(2307

H

)

PLC CPU

monitoring

function

Monitoring condition arrival block No.

0 : The monitoring condition is not enabled for any block

1 to 10: Registration order of word/bit block (nth)

4096 : CPU abnormal monitoring block

The latest block No. for which monitoring condition is enabled is

stored.

0

R

Not allowed

Chapter 2

of User's

Manual

(Application)

8712 to

8954

(2208

H

to

22FA

H

)

8968 to

9215

(2308

H

to

23FF

H

)

Use prohibited

System area