3 transmission control and others monitor/test, Melsec-q, Startup procedure – MITSUBISHI ELECTRIC QJ71C24N User Manual
Page 216: Monitor/test screen] [monitor/test items
8 - 37 8 - 37
MELSEC-Q
8 UTILITY PACKAGE (GX Configurator-SC)
8.6.3 Transmission control and others monitor/test
[Purpose]
Monitor the RS-232 signal status and the various setting values for data
communication.
[Startup procedure]
[Monitor] screen CH Transmission control monitor/test
[Monitor/test screen]
[Monitor/test items]
Monitor/test items
Setting value storage
buffer memory address
Reference section containing
detailed explanation
RTS (RS)
254
H
/264
H
… b0
DSR (DR)
254
H
/264
H
… b1
DTR (ER)
254
H
/264
H
… b2
CD
254
H
/264
H
… b3
CS (CTS)
254
H
/264
H
… b4
RS-232 control
signal status
RI (CI)
254
H
/264
H
… b5
Section 4.4.1 of
User's Manual (Basic)
Communication protocol status
252
H
/262
H
Operation setting
253
H
/263
H
… b0
Data bit
253
H
/263
H
… b1
Parity bit enable/disable
253
H
/263
H
… b2
Even/odd parity
253
H
/263
H
… b3
Stop bit
253
H
/263
H
… b4
Sum check code
253
H
/263
H
… b6
Write during RUM
253
H
/263
H
… b6
Transmission
status
Setting modification
253
H
/263
H
… b7
Section 4.5.2 of
User's Manual (Basic)