Melsec-q, 10 troubleshooting – MITSUBISHI ELECTRIC QJ71C24N User Manual
Page 272

10 - 21 10 - 21
MELSEC-Q
10 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Error Contents
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
7F69
H
Parity error
•
Data does not match the parity bit setting.
•
A malfunction occurred in the network because the
power source of the partner station was on or off.
•
Noise occurs in the network.
•
When the multidrop was connected, data was
transmitted simultaneously by multiple devices.
P/S
•
Match the Q series C24 and
external device settings.
•
Clear the error information
according to the error
information initialization request
(YE/YF).
In addition, when
communicating data with the
non procedure protocol, execute
the INPUT instruction, and read
and discard the unnecessary
data.
•
Measure the noise.
•
When connecting the multidrop,
remove the interlock so that
data will not be transmitted
simultaneously by multiple
devices.
7F6A
H
Buffer full error
•
OS receive buffer overflowed and receive data was
skipped.
SIO
•
Use DTR and DC control and
perform data communications
so that the buffer does not
become full. (Perform RS
⋅
CS
control when the modem
function is used.)
•
If the Read Request signal was
turned ON, execute read
immediately.
7F6B
H
CD signal control
error
•
Data was received when CD signal is OFF when
"CD terminal check enabled" was designated.
CHn
ERR.
•
Recheck the CD signal control
of the external device.
(Send while the CD signal is ON.)
•
Set "no CD terminal checking"
and perform communication.
7F6C
H
Transmission error
•
Data cannot be sent because the line is not
connected.
CHn
ERR.
•
Transmit data after line
connection processing on the
interface side that uses the
modem function.
7F91
H
to
7F96
H
7F98
H
to
7F9A
H
7F9D
H
7F9E
H
7FA0
H
to
7FA3
H
7FA8
H
7FAA
H
to
7FAD
H
7FAF
H
to
7FB2
H
7FB5
H
7FB6
H
7FB8
H
to
7FBC
H
7FC0
H
to
7FC4
H
System error
•
The OS of the Q series C24 detected some error.
—
(
1)