10 TROUBLESHOOTING

Error code

(Hexa-

decimal)

Error

Error Contents

Signal

name

Corrective action

Reference section

There is an error in the designation of the user frame

number.

Recheck the user frame number.

Designate the registered user frame

number.

Register the designated data for

initialization.

Section 3.4.3

Section 3.4.4

Section 3.4.5

7FE1

H

There is an error in the designation of the output head

pointer.

Designate the output head pointer in

the range of 1 to 100.

Designate the position (n-th position)

where the data for initialization number

is designated.

Designate the data for initialization

number at the designated position

(n-th position).

7FE2

H

There is an error in the designation of the output frame

number.

Designate a registered data for

initialization number within the range of

the designated number of outputs from

the location of the output head pointer.

Section 3.4.5

7FE3

H

There is an error in the designation of the number of

registered data bytes.

Designate the data for initialization in

the range of 1 to 78.

Designate 80 for the data for

connection.

Section 3.4.3

Section 3.4.4

7FE4

H

There is an error in the data for connection.

Recheck the message length of the

message for notification.

Section 3.4.4

7FE5

H

There is an error in the designation of the no-

communication interval time.

Designate the no-communication

interval time in the range of 0 to 120.

Section 3.3.6

7FE8

H

The number of remote password mismatch exceeded

the value designated at the address 200D

H

.

Clear the storage area of the

Accumulated count of unlock process

abnormal completion (address: 22FC

H

)

to 0.

Section 3.3.3

7FE9

H

Modern

function

error

Callback denial exceeded the value designated at the

address 2002

H

CHn

ERR.

Clear the storage area of the callback

denial accumulated count (address:

22F1

H

) to 0.

Section 3.3.4

1 Take corrective action in the following procedure.

1) Check whether the Q series C24, power supply module and CPU module are

mounted correctly on the base unit.

2) Check whether the operating environment of the Q series C24 is within the

general specifications range of the CPU module.

3) Check whether the power supply capacity is sufficient or not.

4) Check whether the hardware of the Q series C24, CPU module and base unit

are normal according to the manuals of the corresponding modules.

If any module is faulty, please contact your local Mitsubishi service center or

representative for repair.

5) If the problem cannot be solved through the above steps, please consult your

local Mitsubishi service center or representative, explaining a detailed

description of the problem.