Melsec-q, 10 troubleshooting – MITSUBISHI ELECTRIC QJ71C24N User Manual
Page 273

10 - 22 10 - 22
MELSEC-Q
10 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Error Contents
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
7FC9
H
to
7FCF
H
System error
•
The OS of the Q series C24 detected some error.
(
1)
7FE6
H
•
Remote passwords do not match.
•
Check the remote password and
communicate again.
7FE7
H
•
The remote password is not registered.
•
The remote password processing command was
received on the interface side where the modem
function is not used.
•
The GX Developer connection is selected in the
communication protocol setting on the
corresponding CH.
CHn
ERR.
•
A remote password processing
command is not necessary
when a remote password is not
registered.
•
Perform a remote password
unlock processing through GX
Developer. Alternatively, change
the communication protocol
setting of the corresponding CH
to the MC protocol.
7FE8
H
Processing
disabled
•
The number of remote password disagreements
exceeded the value designated at the address
200D
H
.
CHn
ERR.
•
Clear the storage area of the
cumulative number of abnormal
completions of unlock processing
(address: 22FC
H
) to 0.
7FEF
H
Switch setting error
•
There is an error in the switch setting by the GX
Developer
CHn
ERR.
•
Write CPU to the parameter and
reboot after correcting the
setting value for the switch.
7FF0
H
Dedicated
instructions
simultaneous
execution error
•
Executed dedicated instructions simultaneously.
•
Do not use dedicated
instructions simultaneously.
7FF1
H
Control data error
•
Setting value is incorrect.
•
Setting value is out of range.
•
Correct the setting value in the
control data.
7FF2
H
Communication
protocol setting
error
•
Instruction cannot be executed with the current
communication protocol.
•
Correct the setting value of the
communication protocol.
7FF3
H
to
7FF4
H
System error
•
The OS of the Q series C24 detected some error.
—
(
1)
7FF5
H
Processing
canceled due to
mode
switching/transmiss
ion sequence
initialization
•
The processing was canceled due to mode
switching or receive data clear executed during the
processing.
•
Do not execute mode
switching/receive data clear
during any processing.
7FF7
H
Simultaneous
access error
•
Multiple external devices accessed a remote station
on the same network at the same time.
•
Multiple external devices must
not access a remote station on
the same network at the same
time.
7FF8
H
7FFF
H
System error
•
The OS of the Q series C24 detected some error.
—
(
1)
B000
H
to
BFFF
H
•
Errors detected by the CC-Link module
—
•
Take corrective action by
referring to the CC-Link
Master/Local Module User's
Manual.
C000
H
to
CFFF
H
•
Errors detected by the Ethernet module
—
•
Take corrective action by
referring to the Ethernet
Interface Module User's Manual.
F000
H
to
FFFF
H
•
Errors detected by the MELSECNET/H,
MELSECNET/10 network system
•
Take corrective action by referring
to MELSECNET/H,
MELSECNET/10 network system
reference manual.