9 - 3 9 - 3

MELSEC-Q

9 DEDICATED INSTRUCTIONS

Function

(1) Data stored in the device designated in (S2) and succeeding devices are sent

according to the control data of the device designated in (S1) and succeeding

devices, via the on-demand function of the MC protocol of the module designated in

Un.

(S2)+ 0

+ 1

+ 2

b15

b0

to

Channel 1

Channel 2

QCPU

Q series C24

Send

Send

Channel to be
used is set by
the control data.

(2) When an ONDEMAND instruction is executed on a channel, other ONDEMAND

instructions cannot be executed on that channel at the same time.

If an attempt is made during execution of an ONDEMAND instruction to execute

another ONDEMAND instruction, the second instruction will not be executed until

the execution of the first instruction is completed.

(3) Whether an ONDEMAND instruction was completed normally or abnormally can

be checked by the completion device ((D)) or status display device at completion

((D)+1).

(a) Completion device : Turns on at the END processing of the scan where

the ONDEMAND instruction is completed, and turns

off at the next END processing.

(b) Status display device

at completion

: Turns on and off depending on the completion status

of the ONDEMAND instruction.

• Normal completion : Off with no change.

• Abnormal completion: Turns on at the END

processing of the scan where

the ONDEMAND instruction

is completed, and turns off at

the next END processing.

[Operation during execution of an ONDEMAND instruction]

Sequence
program

ONDEMAND
instruction

Completion device

Status display device
at completion

END
processing

END
processing

Execution of ONDEMAND
instruction

Completion of reading user frame
by ONDEMAND instruction

ON

ON

Abnormal
completion

Normal

completion

One scan

OFF

OFF

END
processing

END
processing