2 commissioning operations, 1 movement test, Commissioning operations – Festo Контроллер позиционирования CPX-CMAX User Manual
Page 94: Movement test, Section 3.2
3. Drive functions
3−32
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH
3.2
Commissioning operations
3.2.1
Movement test
The movement test is for detecting defects in the tubing conĆ
nection.
Note
If the tubing connections of the VPWP get mixed up, the
control direction is reversed. When activating the conĆ
troller, the drive would move at maximum speed into the
end position.
Carry out the movement test in the following cases:
·
During commissioning after parametrisation. The CMAX
expects the movement test to be carried out after
parametrisation and indicates this by showing C03 on
the display.
·
When components are exchanged or the tubing connecĆ
tion has been disconnected and reconnected.
Special cases:
ć
If the movement test is to be skipped (not recommended),
the status of the movement test must be set accordingly.
ć
The movement test status is automatically reset by the
CMAX in the event of faults E01 and E08.
ć
If a movement test is to be carried out at a later time
(e.g. after exchanging hardware), the status of the moveĆ
ment test might have to be reset manually.