1 ccon/scon structure, Ccon/scon structure, Sections 2.2.1 – Festo Контроллер позиционирования CPX-CMAX User Manual

Page 36

background image

2. I/O data and sequence control

2−8

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

2.2.1

CCON/SCON structure

CCON

With control byte 1 (CCON), all the states are controlled which
must be available in all operating modes.

Assignment of the CCON control byte (byte 1)

CCON

B7
OPM2

B6
OPM1

B5
LOCK

B4
ć

B3
RESET

B2
BRAKE

B1
STOP

B0
ENABLE

Operating mode
selection

Software
access
blockage

ć

Reset
fault

Release
brake

Stop

Enable
drive

SCON

Control byte 1 (SCON) signals the CMAX status in all operating
modes.

Assignment of the SCON control byte (byte 1)

SCON

B7
OPM2

B6
OPM1

B5
FCT_MMI

B4
24VL

B3
FAULT

B2
WARN

B1
OPEN

B0
ENABLED

Acknowledgement of
operating mode

Device
control
software

Load
voltage
applied

Fault

Warning

OperĆ
ation enĆ
abled

Drive enĆ
abled

The operating mode is defined with CCON.OPM1 and OPM2
and is acknowledged in SCON.OPM1 and OPM2.

How the control bits work together can be found under the
sequence control description in section 3.